Three Phase Power Quality Analyzer
Features
Safety: CAT III 1000V / CAT IV 600V
Standards: IEC61000-4-30 (2008) S class, EN50160 (2007)
Easy operation to capture the power quality problem
Single-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W
Display: Run Chart, Bar Chart, Vector Graphic, Waveform, Event List, Readings.
8G Memory Card to make the long-term measuring data storage
Support USB port to connect to PC and analyze the data/screen shots copied by U-disk
Support LAN port to make the remote control available, transfer the measuring data
Specifications
| Measurement Range | Resolution | Accuracy | |
Voltage/Current/Frequency | |
Channel | 3-phase line input + 1 neutral line input | |
Vrms(dc+ac) | 1 ~ 1000Vrms | 0.1Vrms | ±5% | |
Vpk | 1 ~ 1400Vpk | 0.1Vpk | ±5% | |
V(CF) | 1.0 ~ >2.8 | 0.01 | ±5% | |
Arms | 1~ 3000A | 1A | ±1% ± 5digits | |
1~ 300A | 0.1A | ±1% ± 5digits | |
Apk | 1 ~ 4000Apk | 1A | ±1% ± 5digits | |
A(CF) | 1 ~ 10 | 0.01 | ±5% | |
Frequency | 42.5~57.5Hz(50Hz nominal) | 0.01Hz | ±0.01% | |
51~69Hz(60Hz nominal) | 0.01Hz | ±0.01% | |
Dips & Swells | |
Vrms1/2 | 0 ~ 200% of nominal voltage | 0.1Vrms | ±1% | |
Arms1/2 | 1 ~ 3000A | 1A | ±1% ±5 counts | |
1 ~ 300A | 0.1A | ±1% ±5 counts | |
Threshold levels | Programmable thresholds in percent of nominal voltage Event detection based upon ½ cycle rms voltages Captures Dips, Swells Interruptions and Rapid Voltage Changes | |
Duration | hhh,mm,ss,mmm | 0.5 cycle | 1 cycle | |
Harmonic | |
Harmonic Order | 1 ~ 50 | | | |
Inter-Harmonic Order | 1 ~ 49 | | | |
Voltage | 0.0 ~ 100.0% | 0.1% | ±0.1% ± nx0.1% | |
Current | 0.0 ~ 100.0% | 0.1% | ±0.1% ± nx0.1% | |
THD | 0.0 ~ 100.0% | 0.1% | ±2.5% | |
DC Relative | 0.0 ~ 100.0% | 0.1% | ±2% | |
Frequency | 0 ~ 3500Hz | 1Hz | 1Hz | |
Phase | -360° ~ 0° | 1° | ± nx1.5° | |
Power And Energy | |
Active Power/Apparent Power/Reactive Power | 1.0 ~ 20.00MW | 0.1kW | ±1.5±10 counts | |
|
Energy | 0.00kWh ~ 200GWh | 10Wh | ±1.5±10 counts | |
Power Factor | 0 ~ 1 | 0.01 | ±0.03 | |
Flicker | |
Pst(1min),Pst,Plt,PF5 | 0.00 ~ 20.00 | 0.01 | ±5% | |
Unbalance | |
Voltage | 0.0 ~ 5.0% | 0.1% | ±0.5% | |
Current | 0.0 ~ 20.0% | 0.1% | ±1% | |
Voltage Phase Angle | -360° ~ 0° | 1° | ±2digits | |
Current Phase Angle | -360° ~ 0° | 1° | ±5digits | |
Voltage Transient | |
Vpk | ±6000Vpk | 1V | ±15% | |
Vrms | 10 ~ 1000Vrms | 1V | ±2.5% | |
Min. Tested Time | 50us | |
Sampling Rate | 20kS/s | |
Inrush Current | |
Arms(AC+DC) | 0~3000Arms | 0.1 | ±1% ± 5digits | |
Inrush Duration | 6s ~ 32min selectable | 10ms | ±20ms | |
Logger | |
Recording | Parameter, duration time and time interval can be set by user, which can be export on PC | |
Memory | 8G | |
Max. recording time | 1 year | |
System Monitor | |
Parameters | Vrms,Arms,Harmonic Volts,THD Volts,Plt,Vrms1/2,Arms1/2,Vneg,Hz,dips and swells, unbalance | |
Record Time | 2h ~ 7days | |
Record Event Number | >10000 | |
Limits | According EN50160 or customer definable | |